Title: Utilização da frequência de 915 MHz para monitoramento e supervisão de isoladores poliméricos classe de tensão de 500 kv
???metadata.dc.creator???: Silva, Huederson Aparecido Botura da 
???metadata.dc.contributor.advisor1???: Mota, Alexandre de Assis
???metadata.dc.contributor.referee1???: Mota, Lia Toledo Moreira
???metadata.dc.contributor.referee2???: Berni, Mauro Donizeti
???metadata.dc.description.resumo???: Em um sistema de transmissão de energia elétrica, os isoladores estão diretamente associados ao nível de segurança da rede, na qual sua falha influência em indicadores das concessionárias. Os isoladores poliméricos estão adquirindo com o passar dos anos maior utilização, sendo que possui inúmeras vantagens perante seus concorrentes (vidro e/ou porcelana), entretanto sua vida útil ainda não pode ser determinada. Este trabalho aborda a utilização da frequência livre de 915 MHz para monitoramento e supervisão destes isoladores poliméricos, sendo possível assim fornecer dados sobre a rede bem como indicando a sua vida útil. Foi realizado uma transmissão de dados mediante variações da intensidade do campo elétrico decorrentes do terminal fase do isolador da classe de tensão de 500 kv. A variação da intensidade do campo elétrico foi obtido utilizando anéis anti-corona diferentes, sendo seus valores obtidos através de simulações utilizando os softwares Gmsh e GetDP que utiliza o método dos elementos finitos. Foi possível observar que a frequência central da portadora não teve variação quando o sinal passava pelo campo elétrico, além de ser possível realizar a comunicação entre os nós sensores tendo, na configuração mais crítica, uma perda de pacotes igual a 1,6%. Também foi possível observar que para todos os ensaios realizados ocorreu pequena degradação do sinal durante a transmissão de dados.
Abstract: In an eletric power transmission system, the insulators are directly associated with the security level of the web, which your fail influence on companies statistics. The polymeric insulators are become more utilized year after year, having numerous advantages to its competitors (glass and/ or porcelain), however, its useful life can not be determined yet. This paper discuss the use of the free frequency of 915 MHz for monitoring and supervision af this polymeric insulators, and can thus provide data about the web, as well, indicate its useful live. Was performed a data transmission with variations of the intensity of eletric fields resulting from the line fitting of the 500kv rated voltage insulator. The variation of the electric field was obtained using different anti-corona rings. Its values were obtained using software as Gmsh and GetDP which use the method of finites elements. Was possible to observe that the central frequency of the carrier didi not change when a sign passed throw the electric field, besides being possible to perform the communication between the sensors having, at the most critical configuration, a packet loss equal to 1,6%. Also was possible observerd that for all tests performed occurred a small degradation of the sign during the data transmission.
Keywords: campo elétrico
isolador polimérico
frequência 915 MHz
smart-grid
gmsh
field eletric
isolator polimeric
frequency 915 MHz
smart-grid
Gmsh
???metadata.dc.subject.cnpq???: CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA::TELECOMUNICACOES
Language: por
???metadata.dc.publisher.country???: BR
Publisher: Pontifícia Universidade Católica de Campinas
???metadata.dc.publisher.initials???: PUC-Campinas
???metadata.dc.publisher.department???: CEATEC – Centro de Ciências Exatas, Ambientais e de Tecnologias
???metadata.dc.publisher.program???: Programa de Pós-Graduação em Engenharia Elétrica
Citation: SILVA, Huederson Aparecido Botura da. Utilização da frequência de 915 MHz para monitoramento e supervisão de isoladores poliméricos classe de tensão de 500 kv. 2012. 273 p. Dissertação (Mestrado em Engenharia Elétrica) - Pontifícia Universidade Católica de Campinas, Campinas, 2012.
???metadata.dc.rights???: Acesso Aberto
URI: http://tede.bibliotecadigital.puc-campinas.edu.br:8080/jspui/handle/tede/537
Issue Date: 7-Dec-2012
Appears in Collections:Programa de Pós-Graduação em Engenharia Elétrica - Mestrado

Files in This Item:
File SizeFormat 
Huederson Aparecido Botura da Silva.pdf8.99 MBAdobe PDFDownload/Open Preview


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.